Scope of Application:
The transformer is fitted with O.L.T.C(on-load tap-changer). And it especially is the same with place which needs steady voltage and variational electrical power system.
Features of production:
Superior performance gets to the international level. It can save energy perfectly. Comparing to GB6451-1999, its no-load loss drops by 30% in average, the load loss drops by 22.4% in average. The production'score of voltage regulater is (±4×2.5%), and has automatica tap-changerlarger than old. It has strongpoint of lower core, temperature and stronger over loading. Firm configuration and good at anti-short circuit performance. The corrugated iron is made of imported steel plate and made with imported equipment, good-looking, workable, durable. Tank and clamps go through acid picking and phosphorization, painting for times after rust frss processing, to make the paint film keep on. |
|
SZ11-200~1600/10 power-transformer with O.L.T.C. |
|
Rated Capacity(kVA) |
200 |
250 |
315 |
400 |
500 |
630 |
800 |
1000 |
1250 |
1600 |
|
connection team mark |
Yyn0 or Dyn11
|
|
no-load loss (w) |
0.33 |
0.40 |
0.48 |
0.57 |
0.68 |
0.88 |
1.05 |
1.25 |
1.45 |
1.85 |
|
load loss (w) |
2.60 |
3.05 |
3.65 |
4.30 |
5.15 |
6.50 |
8.30 |
10.85 |
12.6 |
15.2 |
|
no-load current (%) |
0.8 |
0.7 |
0.7 |
0.6 |
0.6 |
0.6 |
0.6 |
0.6 |
0.6 |
0.6 |
|
impedance voltage (%) |
4 |
4 |
4 |
4 |
4 |
4.5 |
4.5 |
4.5 |
4.5 |
4.5 |
|
weight of core and winding assembly (kg) |
690 |
875 |
950 |
1080 |
1285 |
1445 |
1915 |
2245 |
3325 |
3935 |
|
Oil-weight(kg) |
175 |
205 |
225 |
260 |
275 |
355 |
505 |
557 |
680 |
690 |
|
weight(kg) |
1095 |
1150 |
1220 |
1570 |
1870 |
2140 |
2715 |
3400 |
3810 |
4690 |
figuration size (mm)
|
L |
1680 |
1730 |
1800 |
1850 |
1870 |
1950 |
2300 |
2410 |
2530 |
2580 |
W |
670 |
780 |
860 |
950 |
1050 |
1060 |
1070 |
1150 |
1210 |
1280 |
H |
1420 |
1470 |
1570 |
1620 |
1670 |
1750 |
2090 |
2200 |
2260 |
2350 |
setting size(mm)
|
E1 |
550 |
550 |
550 |
550 |
660 |
660 |
820 |
820 |
820 |
820 |
E2 |
550 |
550 |
550 |
550 |
660 |
660 |
820 |
820 |
820 |
820 |
D |
19 |
19 |
19 |
19 |
19 |
19 |
19 |
19 |
19 |
19 |
bushing size(mm)
|
H1 |
1155 |
1175 |
1265 |
1305 |
1355 |
1395 |
1550 |
1655 |
1725 |
1875 |
h |
905 |
925 |
1015 |
1055 |
1105 |
1145 |
1300 |
1405 |
1475 |
1625 |
h1 |
250 |
250 |
250 |
250 |
250 |
250 |
250 |
250 |
250 |
250 |
h2 |
160 |
160 |
160 |
160 |
260 |
270 |
270 |
330 |
330 |
330 |
h3 |
160 |
160 |
160 |
160 |
160 |
160 |
160 |
270 |
270 |
270 |
L1 |
250 |
250 |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
400 |
L2 |
120 |
120 |
120 |
120 |
160 |
160 |
160 |
200 |
200 |
220 |
L3 |
120 |
120 |
120 |
120 |
160 |
160 |
160 |
200 |
200 |
200 |
B1 |
135 |
140 |
140 |
140 |
160 |
165 |
175 |
190 |
200 |
215 |
B2 |
130 |
140 |
140 |
140 |
145 |
150 |
150 |
150 |
170 |
175 |
low-voltage phase terminal (mm)
|
picture |
(二) |
(二) |
(三) |
(三) |
(四) |
(四) |
(四) |
(四) |
(四) |
(四) |
b |
|
|
|
|
80 |
80 |
80 |
100 |
100 |
100 |
b1 |
|
|
|
|
45 |
45 |
45 |
45 |
45 |
45 |
d |
|
|
|
|
14.5 |
14.5 |
14.5 |
14.5 |
14.5 |
14.5 |
δ |
|
|
|
|
15 |
15 |
15 |
18 |
18 |
18 |
low-voltage zero-line terminal (mm)
|
picture |
(二) |
(二) |
(三) |
(三) |
(三) |
(三) |
(三) |
(四) |
(四) |
(四) |
b |
|
|
|
|
|
|
|
80 |
80 |
80 |
b1 |
|
|
|
|
|
|
|
45 |
45 |
45 |
d |
|
|
|
|
|
|
|
14.5 |
14.5 |
14.5 |
δ |
|
|
|
|
|
|
|
15 |
15 |
15 |
|
| Skeleton map of on-load tap-changer |
|
|