Home > Products > S9 Series Transformer  

Scope of Application:

  Product makes use of any power supply location as well as European Box-transformer, mobile transformer substation and so on.

Features of production:
   Superior performance gets to the international level. It can save energy in evidence. Comparing to GB6451-1999, its no-load loss drops by 11.8% in average, the load loss drops by 22.4% in average. Firm configuration and good at anti-short circuit performance. The corrugated iron is made of imported steel plate and made with imported equipment, good-looking, workable, durable. Tank and clamps go through acid picking and phosphorization, painting for times after rust frss processing, to make the paint film keep on.
S9-30~1600/10 power-transformer
Rated Capacity(kVA)
30
50
80
100
125
160
200
250
315
400
500
630
800
1000
1250
1600
connection team mark
Yyn0 or Dyn11
no-load loss (w)
0.13
0.17
0.25
0.29
0.34
0.40
0.48
0.56
0.67
0.80
0.96
1.20
1.40
1.70
1.95
2.40
load loss (w)
0.60
0.87
1.25
1.50
1.80
2.20
2.60
3.05
3.65
4.30
5.15
6.20
7.5
10.3
12.0
14.5
no-load current (%)
2.1
2.0
1.8
1.6
1.5
1.4
1.3
1.2
1.1
1.0
1.0
0.9
0.8
0.7
0.6
0.6
impedance
voltage (%)
4
4
4
4
4
4
4
4
4
4
4
4.5
4.5
4.5
4.5
4.5
weight of core and winding assembly (kg)
165
210
260
310
355
470
550
640
760
840
1050
1260
1670
1850
2160
2550
Oil-weight(kg)
75
95
115
120
130
145
175
205
245
255
295
355
495
605
625
795
weight(kg)
285
360
470
490
640
740
870
1000
1190
1250
1630
1940
2590
3060
3380
4270
figuration size (mm)
L
970
1040
1110
1140
1250
1290
1350
1390
1480
1530
1570
1650
2100
2180
2270
2480
W
520
620
620
620
620
620
640
670
750
790
850
1020
1030
1100
1160
1540
H
1060
1060
1140
1160
1300
1330
1370
1410
1460
1530
1560
1640
2040
2170
2270
2300
setting size (mm)
E1
400
400
400
400
550
550
550
550
550
550
660
660
820
820
820
820
E2
400
400
400
400
550
550
550
550
550
550
660
660
820
820
820
820
D
14
14
14
14
19
19
19
19
19
19
19
19
19
19
19
19
bushing size(mm)
H1
875
885
940
965
1045
1055
1105
1135
1195
1265
1295
1375
1550
1675
1785
1855
h
625
635
690
715
795
805
855
885
945
1015
1045
1125
1300
1425
1535
1605
h1
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
h2
125
125
125
125
125
125
160
160
160
160
260
270
270
330
330
330
h3
125
125
125
125
125
125
160
160
160
160
160
160
160
270
270
270
L1
180
200
200
200
200
200
250
250
300
300
300
300
300
300
300
400
L2
100
100
100
100
100
100
120
120
120
120
160
160
160
200
200
220
L3
100
100
100
100
100
100
120
120
120
120
160
160
160
160
160
200
B1
80
90
95
100
100
110
120
130
140
140
150
150
175
190
200
210
B2
85
98
100
105
110
120
120
125
130
135
140
140
145
150
150
170
low-voltage phase terminal(mm)
picture
(一)
(一)
(一)
(一)
(一)
(一)
(二)
(二)
(三)
(三)
(四)
(四)
(四)
(四)
(四)
(四)
b
80
80
80
100
100
100
b1
45
45
45
45
45
45
d
14.5
14.5
14.5
14.5
14.5
14.5
δ
15
15
15
18
18
18

low-voltage zero-line terminal (mm)
picture
(一)
(一)
(一)
(一)
(一)
(一)
(二)
(二)
(三)
(三)
(三)
(三)
(三)
(四)
(四)
(四)
b
80
80
80
b1
45
45
45
d
14.5
14.5
14.5
δ
15
15
15
 S9-M Series Sealed Transformer    
点击放大图片